Frame size: 2000AF.
Rated Current, In (A): 630, 800, 1000, 1250, 1600, 2000.
Pole: 3P, 4P.
Frequency: 50/60Hz.
Rated Voltage, Ue: 690V.
.
Breaking capacity:
Model | HS | HN | |
Icu/Ics (kA) | 240V | 80/50 | 85 |
380/400/415V | 80/50 | 85/85 | |
690V | 50/50 | 55/55 | |
Icw (kA) 1sec |
400/415V | 50 | 65 |
690V | 50 | 65 |
Endurance:
Rated Current (A) | 630/800/1000 | 1250/1600/2000 | |
Mechanical | With Maintenance | 20,000 | |
Without Maintenance | 15,000 | ||
Electrical | With Maintenance | 15,000 | |
Without Maintenance | 8,000 |